Starting at $255.16
  • Usually ships in 2-3 weeks

Overview

Features

  • Power supply: 20 to 250 V AC/DC
  • Loop power supply: 8 V DC
  • Function: 2-channel, changeover contact
  • Certificates
    • ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1) D [Ex ia Da] IIIC, II3G Ex ec nC IIC Gc
    • DNV
  • For ambient temperatures -40 to 140°F (-40 to 60°C)

Description

The E+H RLN42 NAMUR isolating amplifier is designed for operation of proximity switches according to EN 60947-5-6 (NAMUR) as well as open and mechanical contacts with resistive coupling elements. It has a universal power supply (24 to 230 V AC/DC) and one relay output (changeover) per channel. The device is approved for intrinsically safe (Ex i) circuits up to zone 0 (gas) and zone 20 (dust) in the Ex area. RLN42 can be used in safety equipment up to SIL 2 in accordance with IEC 61508.

This isolating amplifier monitors the input circuits for line faults, such as line breaks and short-circuits (LFD). It is disengageable. Contains input for proximity sensors acc. to NAMUR (EN 60947-5-6); floating contacts or contacts with resistance circuit. The output-side relay contacts as signal output, direction of action can be selected via DIP switches. Configurable with resistive coupling element for line monitoring of mechanical switching contacts.