• 2141.02
  • Usually ships in 1-2 weeks

Overview

Features

  • Current range: 0.2mA to 40A
  • Resistance range: 0.01 to 1500Ω
  • Test frequency selection
  • Touch voltage indication
  • Loop resistance indication
  • Sores up to 2000 measurements
Interested in a FREE demo? Call 1-800-884-4967 or complete this form to submit your request.

Description

The AEMC Model 6417 Clamp-On Ground Resistance Tester measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test it. The Model 6417 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.

The DataView® software included provides the ability to configure and retrieve data from the Model 6417 through Bluetooth® communication, as well as the ability to generate reports.

The 6417 includes a high sensitivity measurement function enabling measurement of leakage current flowing to ground or circulating in ground loops from 0.2mA to 40A and resistances from 0.01 to 1500Ω. It also offers battery life information at power-up and Auto Power OFF power management. The Buzzer and Auto Power OFF features may be disabled at any time. There are alarm and data storage functions, which are saved when the tester is turned off.

Applications

This product can be used in the following applications: