AEMC 3711 Ground Resistance Tester
Clamp-on ground resistance tester with measurement range from 0.1 Ω to 1200 Ω.
Overview
Features
- Direct reading of ground resistance from 0.1 Ω to 1200 Ω
- Measure down to 0.1 Ω with resolution of 0.01 Ω
- Direct reading of continuity and ground loop resistance
- Direct reading of ground leakage or phase current from 1 mA to 30 A RMS
- Jaw design with large 1.25" (32 mm) window - accomodates up to 1000 kcmil cables
- Auto-off for power management
- Meets EN 61010, Cat III
- CE Mark and UL approved and double insulated
- Fast settling time (approximately one second)
- High immunity to electrical noise for work around transmission towers and substations
Description
The AEMC 3711 clamp-on ground resistance tester measures ground rod and grid resistance in any environment without the use of auxiliary ground rods. Clamp-on ground resistance testers are used on multi- grounded systems without disconnecting the ground under test. The simply clamps around the ground conductor or rod and measures the resistance to ground fast and accurately.
The AEMC 3711 clamp-on ground resistance tester includes a current measurement function. The probe's high sensitivity enables measurement of leakage current flowing to ground or circulating in ground loops down to 1 mA as well as neutral and phase currents to 10 A RMS. This feature provides additional information, which is vital in distribution ground networks carrying higher levels of noise and harmonics, that affect power quality.
Applications for the AEMC 3711 clamp-on ground resistance tester:
- Measure electrical ground rod and grid resistance
- Use on multi-grounded systems without disconnecting the ground rod under test
- Measure resistance and continuity of grounding loops around pads and buildings
- Measure leakage current flowing to ground or circulating in ground systems
The AEMC 3711 clamp-on ground resistance tester ships complete with:
- Calibration loop
- 9V Battery
- Hard case
- Manual
AEMC 3711 Clamp-on Ground Resistance Tester Specifications | |||
---|---|---|---|
Ground resistance ranges Auto-ranging 0.01 to 1200 Ω |
Measurement range | Resolution | Accuracy (% of reading) |
0.10 to 1.00 Ω | 0.01 Ω | ±(2% ±0.02 Ω) | |
1.0 to 50.0 Ω | 0.1 Ω | ±(1.5% ±0.1 Ω) | |
50.0 to 100.0 Ω | 0.5 Ω | ±(2% ±0.5 Ω) | |
100 to 200 Ω | 1 Ω | ±(3% ±1 Ω) | |
200 to 400 Ω | 5 Ω | ±(6% ±5 Ω) | |
400 to 600 Ω | 10 Ω | ±(10% ±10 Ω) | |
600 to 1200 Ω | 50 Ω | Approx:25% ±50 Ω | |
Current measurement ranges Auto-ranging 1 mA to 30.00 A RMS |
Measurement range | Resolution | Accuracy (% of reading) |
1 to 299 mA | 1 mA | ±(2.5% + 2 mA) | |
0.300 to 2.999 A | 0.001 A | ±(2.5% + 2 mA) | |
3.00 to 29.99 A | 0.01 A | ±(2.5% + 20 mA) | |
Current measurement frequency | 47 to 800 Hz | ||
Current overload | OL displayed above 29.99 A RMS | ||
Power source | 9V alkaline battery (IEC 6LF22 or NEDA 1604A) | ||
Jaw window diameter | 1.25" (32 mm) | ||
Jaw opening | 1.38" (35 mm) | ||
Safety rating | EN 61010-2-032 (Class 2) Double insulation | ||
Double insulation | Yes | ||
CE mark | Yes |