Overview

Features

  • AC voltage: 600.0 V
    • Accuracy: ±(0.5 % rdg + 5d)
  • DC voltage: 600.0 V
    • Accuracy: ±(0.5 % rdg + 5d)
  • AC current: 40.0 / 400.0 / 1000 A
    • Accuracy: ±(0.5 % rdg + 5d)
  • Frequency: 5.00 Hz to 500.0 Hz
    • Accuracy: ±(0.5% rdg + 4d)
  • Temperature: -58 to 572°F
    • Accuracy: up to ± (2.0% rdg + 3°C)
  • Total harmonic distortion to 51st harmonic
  • Total Power Factor (PF), Power (VA), and Power (kW and kVAR) measurements
  • Optional PC interface capability
  • CAT III 600V safety rating
  • UL listed

What's in the Box

  • Carrying case
  • Test leads
  • Batteries
  • Type-K Thermocouple
  • Manual

Description

The Amprobe ACD-41PQ clamp-on power quality meter provides a simple and effective way to verify if the electrical system is affected by harmonics. The ACD-41PQ is a True RMS clamp-on meter with enhanced troubleshooting capabilities as well as power analysis functions. For enhanced meter functionality an optional PC interface kit is available for data analysis.

Amprobe ACD-41PQ clamp-on power quality meters feature: an audible, continuity alarm; auto power-off; automatic polarity detection; low battery indication; peak hold; data hold and voltage overload protection for all functions up to 600 V AC/DC.

The Amprobe ACD-41PQ clamp-on power quality meter accurately measures AC/DC voltage, AC current, frequency, and temperature. Additionally, the meter measures total harmonic distortion to th 51st harmonic with accuracy from ±(1.5% rdg + 6d) to ±(4.5% rdg + 6d) depending on range. The The Amprobe ACD-41PQ also measures Active (W), Reactive (VAR) and Apparent (VA) Power with dual-display Power Factor readout.