Starting at $333.00
  • Call for availability

Overview

Features

  • Selectable pressure range:
    • 0 to 1, 2, 3 and 4inH2O or
    • 0 to 10, 20, 30 and 40inH2O
  • ±0.5% FS accuracy
  • <0.5% long-term stability
  • Overload limit:
    • 0 to 1 ± 4inH2O
    • 0 to 40 ± 320inH2O
  • -4 to 140°F (-20 to 60°C) temperature range
  • Digital and analog output
  • IP65 / NEMA 4 protection
  • Large graphic display
  • Installation-friendly enclosure

Description

The E+E EE600 differential pressure sensor is a multi-range device that measures air and all non-flammable and non-aggressive gases. The EE600 is available with full scale (FS) 4 inches and 40 inches of water column. In versions with analog outputs, DIP switches allow the user to select several measuring ranges. The piezo-resistive, no flow-through pressure sensing element provides outstanding long-term stability. In addition to differential pressure measurement, the EE600 can be set up for volume flow or air velocity measurement, and for filter monitoring or level indication.

The measured data is available on the analog voltage and current outputs or on the RS485 interface with Modbus RTU or BACnet MS/TP protocol. The IP65 / NEMA 4 enclosure minimizes installation costs. External mounting holes allow for installation with a closed cover, protecting the electronics against construction site pollution.

The setup and adjustment can easily be performed with DIP switches and push buttons on the electronics board, or with an optional adapter and the EE-PCS configuration software. The display includes pressure range, output signal, response time, display units and backlight. A zero and span point adjustment can be easily performed with push buttons on the electronics board.