Overview

Features

  • Sampling Method: Non-dispersive infrared (NDIR), gold plated optics
  • Visual Level Indicator
  • ABC Logic self calibration algorithm
  • Diffusion sampling
  • Measurement Range: 0 to 2,000 ppm factory calibrated.
  • Accuracy: ±75 ppm @ 72°F (22°C)
  • Stability: <2% of FS over life of sensor
  • Non-Linearity: <1% of FS
  • Response Time: 3 to 5 minutes for 90% step change.
  • Analog (0 to 10V) or digital (RS-232) output

Description

The low-cost Telaire T5007 Airestat CO2/temperature transmitter is a wall-mounted sensing solution for demand-controlled ventilation. The T5007 provides an intuitive VLI (Visual Limit Indicator) display for CO2 thresholds, a passive temperature output (20kΩ thermistor), and a standard analog 0 to 10 volt signal to maintain air quality in enclosed spaces (such as school classrooms, offices, gymnasiums, and theaters).

Telaire T5007 features a digital UIP (User Interface Program) to configure internal carbon dioxide concentration thresholds (optional accessory cable and software not included.) The factory defaults are 1000 ppm and 1500 ppm.

The Telaire T5007 employs gold-plated optics for accurate measurements and Telaire's patented ABC (Automatic Background Calibration) Logic™ software for self-correction of drift to better than ±20 ppm per year. The system is virtually free of maintenance and typically has a lifetime of more than 10 years.

Additionally, the T5007 includes Telaire's VLI (Visual Level Indicator) system which communicates intuitively to the average end-user. The correlation between a carbon dioxide PPM reading and adequate ventilation may not be fully understood. Instead of offering the user a reading in PPM, the T5007 provides a simple LED that communicates increased CO2 concentrations based on definable or predetermined thresholds. The LED smoothly transitions between green, yellow and red as the CO2 threshold is exceeded making these units highly intuitive and easy-to-use.